Description
Product Features
1.LCD screen display, clear and easy to operate
2.Double conversion true online design, using DSPI technology, high input power factor
3.Flexible parallel technology is suitable for different loads and systems
4.ECO working mode improves system efficiency
5.Automatically and evenly float the battery to extend battery life
6.Automatically adjust the mains voltage boost, step down and stable voltage output
7.The isolation effect of the output transformer enables the load to reduce harmonic currents and mains interference
8.The delay soft start function effectively reduces the impact on the equipment and the power grid when the system starts
9.Cold start function, UPS battery pack can directly start UPS power when there is no AC power input
10.When the battery power is exhausted during a power failure, the input UPS power will be automatically turned on, and the battery will be automatically charged to ensure stable operation next time.
Input
|
||
Rated Voltage
|
3×400V(3 Phase + N)
|
|
Voltage Range
|
305-478VAC ±3%@100% load 190-520VAC ±3%@50% load
|
|
Frequency Range
|
46-54Hz or 56-64Hz
|
|
Power factor
|
≥0.99 @ 100% load
|
|
Output
|
||
Output Voltage
|
3×400V(3 Phase + N)
|
|
Voltage range (battery mode)
|
±1%
|
|
Frequency range (synchronization correction range)
|
46-54 Hz or 56-64 Hz
|
|
Frequency range (battery mode)
|
50 Hz±0.1 Hz or 60 Hz + 0.1 Hz
|
|
Surge ratio
|
3:1(biggest)
|
|
Harmonic distortion
|
≤2%THD(Pure Load); ≤5%THD(Pure Load)
|
|
Conversion time
|
AC to DC
|
0
|
Inverted to bypass
|
0
|
|
Waveform (battery mode)
|
Pure sine wave
|
|
Efficient
|
||
Mains mode
|
90.5%-91.3%
|
|
ECO mode
|
96.0%
|
|
Show Description
|
||
LCD or LED
|
Load size, battery capacity, mains mode, battery mode, bypass mode, fault indication
|
|
Use Environment
|
||
Temperature and humidity
|
Relative humidity 0-95% and temperature 0-40℃ (non-condensing)
|
|
Noise
|
<60 dB 1 meter
|
<65 dB 1 meter
|
⇒ RELATED PRODUCT
Reviews
There are no reviews yet.